The reference processing method is selected by way of the function selector. The default setting is the function RERV(-2), with which the reference input +/-10 V is evaluated referred to user units.
The parameters are initialized only after the control has been re-enabled or by a device restart.
The selection TLIM(-4) to REFV(-2) is reserved for the analog input function. The other settings can be used for the function as a digital input.
Bild: Analog input function selector (-5) to (-1)
P. no. |
Parameter name Setting |
Function |
---|---|---|
P 0109/ P 0110 |
MPRO_INPUT_FS_ISA00/ISA01 | Reference selector for the analog inputs |
(-5) | Not defined | Not defined |
(-4) | TLIM(-4) |
Torque scaling:
|
(-3) | OVR(-3) | Scaling of the parameterized travel speed in positioning (0 to 10 V corresponds to 0 – 100%). The override is recorded directly after the analog filter. The backlash is not effective for these functions! |
(-2) | REFV(-2) | Reference input +/-10 V referred to user units. |
Tabelle: Reference selector